How to read an electricity number
Eight ideas that make megawatts, gigawatts and kilowatt-hours stop blurring together.
A watt is a speed. A watt-hour is a distance.
Power, in watts, is how fast electricity is flowing right now. Energy, in watt-hours, is how much has flowed in total. The relationship is the same as speed and distance: drive at 60 mph for two hours and you have covered 120 miles.
A microwave draws about 1.1 kW while it runs. Run it for three minutes and it has used 55 Wh of energy. Data centre sizes are quoted in power (MW, GW). Your bill is in energy (kWh).
Watts are not per day, per month or per year.
Because a watt is already a rate, “the US uses 505 GW” means that at any given moment, on average, that is how much the country is drawing. Time only enters when you ask how much energy that adds up to.
There are 8,760 hours in a year, so 505 GW × 8,760 h = 4.43 PWh a year. Going the other way, 1 TWh a year is a steady 114 MW.
Each step is a thousand times bigger.
| W | watt | 1 | A phone charger draws about 5 |
| kW | kilowatt | 1,000 W | A microwave while it runs; an average US home |
| MW | megawatt | 1,000 kW | A large hospital uses about 2; an AI data centre building 50 to 150 |
| GW | gigawatt | 1,000 MW | New York City averages about 6; a large AI campus about 1 |
| TW | terawatt | 1,000 GW | The whole world uses about 3.6; the US about half of one |
The slider on the home page runs up through all of them.
The same thing has three different numbers.
Rated is the most a device can draw or a plant can make. Peak is the highest a place actually reached. Average is the steady level that would use the same energy over a year.
New York City averages 5.78 GW but has peaked at 11.1 GW on a hot afternoon. A home has appliances rated at many kilowatts, yet averages 1.23 kW because most are off most of the time. Always ask which of the three a number is.
A gigawatt of solar is not a gigawatt of nuclear.
Power plants are sold by rated size, but none runs flat out all year. Capacity factor is the share of its rated output a plant really delivers. US fleet averages:
- Nuclear91.1%
- Combined-cycle gas58.7%
- Coal48.8%
- Hydro34.4%
- Wind33.8%
- Solar24%
So matching one reactor's yearly output takes roughly four times its rated size in solar panels, plus storage to cover the night. The “Average output” switch on each item's page applies these.
IT power, facility power, grid connection.
IT power is what the chips and servers draw. Facility power adds cooling and electrical losses. The ratio between them is called PUE: the industry average is 1.54, the best hyperscale fleets reach 1.09. The grid connection is what the utility has agreed to supply, often more than is used on day one.
Announcements rarely say which one they mean, which is why the same campus can be reported at very different sizes. As a rule of thumb, 1 GW of IT power runs about 600,000 current-generation AI GPUs.
Energy is sold by the kWh. Data centre space is sold by the kW.
A utility charges for energy delivered, in cents per kWh. A colocation provider charges for reserved capacity, in dollars per kW per month, because what they are really renting out is a share of their power and cooling plant.
To compare the two, divide by the 730 hours in a month: $172.5/kW-month works out to 23.6¢ per kWh at full load, before the electricity itself.
Be suspicious of “enough to power X homes”.
On average energy, 1 GW running all year equals about 812,000 US homes. But a headline about a new solar farm usually divides its rated size by an average home, ignoring that the farm averages a quarter of that and makes nothing at night.
Homes are also only about a third of electricity use; the rest goes to businesses and industry. A city needs far more power than its homes alone.